DIESEL ENGINE-GENERATOR SET
600-VC6DT2
600 ekW / 60 Hz / Standby
550 ekW / 60 Hz / Prime
208 - 4160V
System Ratings
Standby
Voltage (L-L)
Phase
PF
Hz
kW
kVA
AMPS
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
Prime
Voltage (L-L)
Phase
PF
Hz
kW
kVA
AMPS
skVA@30%
Voltage Dip
wwwGTee.mDnepartRaatiSsoher eMeot4deUl*.c om
Connection
208V**
3
0.8
60
600
750
2082
1750
573RSL4033
130°C/27°C
12 LEAD LOW WYE
208V
3
0.8
60
550
687.5
1908
1750
573RSL4033
105°C/40°C
12 LEAD LOW WYE
240V**
3
0.8
60
600
750
1804
1750
573RSL4033
130°C/27°C
12 LEAD HI DELTA
240V
3
0.8
60
550
687.5
1654
1750
573RSL4033
105°C/40°C
12 LEAD HI DELTA
480V**
3
0.8
60
600
750
902
1450
572RSL4031
130°C/27°C
12 LEAD HI WYE
480V
3
0.8
60
550
687.5
827
1450
572RSL4031
105°C/40°C
12 LEAD HI WYE
600V**
3
0.8
60
600
750
722
1450
572RSS4272
125°C/40°C
4 LEAD WYE
600V
3
0.8
60
550
687.5
662
1450
572RSS4272
105°C/40°C
4 LEAD WYE
* The Generator Model Number identified in the table is for standard C Series Configuration. Consult the factory for alternate configuration.
** UL2200 Offered
4160V
3
0.8
60
600
750
104
1550
574FSM4356
130°C/27°C
6 LEAD WYE
4160V
3
0.8
60
550
687.5
95
1550
573FSM4356
105°C/40°C
6 LEAD WYE



No Preview Available !

2 / //  / 600-VC6DT2
Facts
//  EPA Tier 2 Certified
//  Engine-Generator Set Tested to ISO 8528-5 for
Transient Response
//  UL2200, CSA Listing Offered
//  Accepts Rated Load in One Step Per NFPA 110, Level 1
//  All engine-generator sets are prototype and factory tested
//  MTU Onsite Energy is a single source supplier
//  Global Product Support
//  2 Year Standard Warranty
//  Custom Design for Any Application
//  TWD1643GE Diesel Engine
- 16.1 Liter Displacement
- Electronic Unit Pump Injection
- 4-Cycle
STANDARD EQUIPMENT
//  Complete Range of Accessories
//  Permanent Magnet Generator (PMG)
- Brushless, Rotating Field
- 300% Short Circuit Capability
- 2/3 Pitch Windings
//  Digital Control Panel(s)
- UL Recognized, , NFPA 110
- Complete System Metering
- LCD Display
//  Cooling System
- Integral Set-Mounted
- Engine Driven Fan
//  Engine
Air Cleaner
Oil Pump
Full Flow Oil Filter
Jacket Water Pump
Thermostat
Exhaust Manifold – Dry
Blower Fan & Fan Drive
Radiator - Unit Mounted
Electric Starting Motor - 24V
Governor – Electric Isochronous
Base - Structural Steel
SAE Flywheel & Bell Housing
Charging Alternator - 24V
Battery Box & Cables
Flexible Fuel Connectors
Flexible Exhaust Connection
EPA Certified Engine
//  Generator
NEMA MG1, IEEE and ANSI standards compliance for temperature rise
and motor starting
Sustained short circuit current of up to 300% of the rated current for up
tow1w0wse.DcoantdasSheet4U.com
Self-Ventilated and Drip-Proof
Superior Voltage Waveform
Digital, Solid State, Volts-per-Hertz Regulator
No Load to Full Load Regulation
Brushless Alternator with Brushless Pilot Exciter
4 Pole, Rotating Field
130°C Standby Temperature Rise
1 Bearing, Sealed
Flexible Coupling
Full Amortisseur Windings
125% Rotor Balancing
3-Phase Voltage Sensing
±.25% Voltage Regulation
100% of Rated Load - One Step
3% Maximum Harmonic Content
//  Digital Control Panel(s)
Digital Metering
Engine Parameters
Generator Protection Functions
Engine Protection
SAE J1939 Engine ECU Communications
Windows-Based Software
Multilingual Capability
Remote Communications to our RDP-110 Remote Annunciator
16 Programmable Contact Inputs
7 Contact Outputs
UL Recognized,
, CE Approved
Event Recording
IP 54 Front Panel Rating with Integrated Gasket
NFPA110 Level Compatible



No Preview Available !

3 / //  / 600-VC6DT2
Application data
//  Engine
Manufacturer
Model
Type
Arrangement
Displacement: Cu In (lit)
Bore: in (cm)
Stroke: in (cm)
Compression Ratio
Rated RPM
Engine Governor
Max Power: Standby: bhp (kWm)
Max Power: Prime: bhp (kWm)
Regulation
Frequency
Air Cleaner
//  Liquid Capacity (Lubrication)
Total Oil System: gal (lit)
Engine Jacket Water Capacity: gal (lit)
System Coolant Capacity: gal (lit)
//  Electrical
Electric Volts DC
Cold Cranking Amps Under 0°F (-17.8°C)
//  Fuel System
Fuel Supply Connection Size
Fuel Return Connection Size
Maximum Fuel Lift: ft (m)
Recommended Fuel
Total Fuel Flow: gal/hr (lit/hr)
Volvo Penta
TWD1643GE
4-Cycle
6-Inline
984 (16.1)
5.67 (14.4)
6.5 (16.5)
16.5:1
1,800
EMS 2
917 (684)
796 (594)
±.25%
60 Hz
Dry
12.7 (48)
8.7 (33)
25.1 (95)
24
1,155
3/4” NPT
1/2” NPT
3.5 (1)
Diesel #2
55.5 (210)
www.DataSheet4U.com
//  Fuel Consumption
At 100% of Power Rating: gal/hr (lit/hr)
At 75% of Power Rating: gal/hr( lit/hr)
At 50% of Power Rating: gal/hr (lit/hr)
STANDBY
43.1 (163)
31.2 (118)
21.1 (80)
PRIME
37.5 (142)
30.1 (114)
18.5 (70)
//  Cooling - Radiator System
STANDBY PRIME
Ambient Capacity of Radiator: °F (°C) 122 (50) 122 (50)
Max. Restriction of Cooling Air, Intake,
and Discharge Side of Rad.: in. H20 (kPa) 0.8 (0.2)
Water Pump Capacity: gpm (lit/min) 121 (458)
2.4 (0.6)
121 (458)
Heat Rejection to Coolant: BTUM (kW) 15,355 (270) 13,990 (246)
Heat Rejection to After Cooler: BTUM (kW) 7,677 (135) 7,109(125)
Heat Radiated to Ambient: BTUM (kW) 4,327 (76) 3,511 (61.7)
//  Air Requirements
Aspirating: *SCFM (m3/min)
Air Flow Required for Rad.
Cooled Unit: *SCFM (m3/min)
Air Flow Required for Heat
Exchanger/Remote Rad. based
on 25°F Rise: *SCFM (m3/min)
STANDBY PRIME
1,937 (54.9) 1,874 (53.1)
23,277 (659) 23,277 (659)
9,759 (278) 7,917 (226)
* Air density = 0.0739 lbm/ft3 (1.184 kg/m3)
//  Exhaust System
Gas Temp. (Stack): °F (°C)
Gas Volume at Stack
Temp: CFM (m3/min)
Maximum Allowable
Back Pressure: in. H20 (kPa)
STANDBY
862 (461)
PRIME
792 (422)
4,594 (130.1) 4,202 (119)
40.2 (10) 40.2 (10)



No Preview Available !

Weights and dimensions
4 / //  / 600-VC6DT2
Drawing above for illustration purposes only, based on standard open power 480 volt generator. Lengths may vary with other voltages. Do not use for installation design.
System Dimensions (L x W x H)
OPU
140 x 56 x 81.25 in (3,560 x 1,420 x 2,060 mm)
Weight (less tank)
10,064 lb (4,565 kg)
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific generator set.
Sound data
Unit Type
OPU w/Critical Grade Muffler (dBA)
Sound Attenuated Enclosure (dBA)
Measurements for sound data are taken at 23 ft (7 m).
Emissions data
Standby Full Load
99
91
Standby No Load
91
83
Prime Full Load
97.5
89.5
Prime No Load
91
83
Rating Definitions and conditions
NOx + NMHC
4.28
CO
0.31
PM
0.057
All units are in g/hp-hr and are EPA D2 cycle values.
Emission levels of the engine may vary as a function of ambi-
ent temperature, barometric pressure, humidity, fuel type and
quality, installation parameters, measuring instrumentation,
etc. The data provided are laboratory results from one engine
representing this rating. The data was obtained under cont-
rolled environmental conditions with calibrated instrumentation
traceable to the United States National Bureau of Standards
and in compliance with US EPA regulations found within 40 CFR
Part 89. The weighted cycle value from each engine is guaran-
teed to be below the US EPA Standards at the US EPA defined
conditions.
www.DataSheet4U.com
//  Ambient capability factor at 984 ft (300 m). Consult your
local MTU Onsite Energy Power Generation Distributor for
other altitudes.
//  Standby ratings apply to installations served by a reliable
utility source. The standby rating is applicable to varying
loads for the duration of a power outage. No overload capa-
bility for this rating. Ratings are in accordance with
ISO-3046/1, BS 5514, AS 2789, and DIN 6271.
//  Prime power ratings apply to installations where utility power
is unavailable or unreliable. At varying load, the number of
generator set operating hours is unlimited. A 10% overload
capacity is available for one hour in twelve. Ratings are in
accordance with ISO-8528/1, overload power in accordance
with ISO-3046/1, BS 5514, AS 2789, and DIN 6271. For
limited running time and base load ratings, consult the
factory.
//  Deration Factor:
Altitude: 5% per 1,476 ft (450 m) above 4,921 ft (1,500 m).
Temperature: No derate due to increased temperature.
Materials and specifications subject to change without notice.
// Tognum Group Companies: Europe / Middle East / Africa / Latin America / MTU Onsite Energy / 88040 Friedrichshafen / Germany / Phone + 49 7541 90 7060 /
Fax +49 7541 90 7084 / powergenregion1@mtu-online.com // Asia / Australia / Pacific / MTU Onsite Energy / 1, Benoi Place / Singapore 629923 / Republic of Singapore /
Phone + 65 6861 5922 / Fax + 65 6861 3615 / powergenregion2@mtu-online.com // USA / Canada / Mexico / MTU Onsite Energy / 100 Power Drive / Mankato, Minnesota
56001 / USA / Phone + 1 507 625 7973 / Fax + 1 507 625 2968 / powergenregion3@mtu-online.com // Worldwide for HotModule / MTU Onsite Energy / 81663 Munich /
Germany / Phone + 49 89 203042 800 / Fax +49 89 203042 900 / info@cfc-solutions.com //www.mtu-online.com



600-VC6DT2 datasheet pdf
Download PDF
600-VC6DT2 pdf
View PDF for Mobile


Related : Start with 600-VC6DT Part Numbers by