40-GC6NLT1 Datasheet PDF - MTU Onsite Energy

www.Datasheet-PDF.com

40-GC6NLT1
MTU Onsite Energy

Part Number 40-GC6NLT1
Description GAS ENGINE-GENERATOR SET
Page 4 Pages


40-GC6NLT1 datasheet pdf
Download PDF
40-GC6NLT1 pdf
View PDF for Mobile

No Preview Available !

A tognum Group Brand
GAS Engine-Generator Set
40-GC6NLT1
40 ekW / 60 Hz / Standby
208 - 600V
System Ratings
Standby
Voltage (L-L)
Phase
PF
Hz
Natural Gas
Ratings: Amps
Natural Gas
Ratings: kW/kVA
LP Gas
Ratings: Amps
LP Gas
Ratings: kW/kVA
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
240V**
1
1.0
60
240V**
1
1.0
60
146 146
35/35
35/35
167 167
40/40
40/40
128
362CSL1604
130°C/27°C
12 LEAD ZIG-ZAG
102
284CSL1550
125°C/40°C
4 LEAD
208V**
3
0.8
60
139
40/50
139
40/50
93
284CSL1542
130°C/27°C
12 LEAD LOW WYE
240V**
3
0.8
60
480V**
3
0.8
60
120 60
40/50
40/50
120 60
40/50
40/50
93
284CSL1542
130°C/27°C
12 LEAD HI DELTA
133
284CSL1542
130°C/27°C
12 LEAD HI WYE
* The Generator Model Number identified in the table is for standard C Series Configuration. Consult the factory for alternate configuration.
** UL2200 Offered
600V**
3
0.8
60
48
40/50
48
40/50
92
361PSL1632
125°C/40°C
4 LEAD WYE
Facts
//  Engine-Generator Set Tested to ISO 8528-5 for
Transient Response
//  UL2200, CSA Listing Offered
//  Accepts Rated Load in One Step Per NFPA 110, Level 1
//  All engine-generator sets are prototype and factory tested
//  MTU Onsite Energy is a single source supplier
//  Global Product Support
//  2 Year Standard Warranty
//  Custom Design for Any Application
ww/w/  .D4.a3taLSEhneegtin4Ue .com
- 4.3 Liter Displacement
- 4-Cycle
//  Integral Vibration Isolators
//  Complete Range of Accessories
//  Permanent Magnet Generator (PMG) - Optional
- Brushless, Rotating Field
- 300% Short Circuit Capability
- 2/3 Pitch Windings
//  Digital Control Panel(s)
- UL Recognized, , NFPA 110
- Complete System Metering
- LCD Display
//  Cooling System
- Integral Set-Mounted
- Engine Driven Fan



No Preview Available !

2 / //  / 40-GC6NLT1
STANDARD EQUIPMENT
//  Engine
Air Cleaner
Oil Pump
Full Flow Oil Filter
Jacket Water Pump
Thermostat
Exhaust Manifold – Dry
Blower Fan & Fan Drive
Radiator - Unit Mounted
Electric Starting Motor - 12V
Governor – Electric Isochronous
Base - Formed Steel
SAE Flywheel & Bell Housing
Charging Alternator - 12V
Battery Box & Cables
Flexible Fuel Connectors
Flexible Exhaust Connection
EPA Certified Engine
//  Digital Control Panel(s)
Digital Metering
Engine Parameters
Generator Protection Functions
Engine Protection
SAE J1939 Engine ECU Communications
Windows-Based Software
Multilingual Capability
Remote Communications to our RDP-110 Remote Annunciator
16 Programmable Contact Inputs
7 Contact Outputs
UL Recognized,
, CE Approved
Event Recording
IP 54 Front Panel Rating with Integrated Gasket
NFPA110 Level Compatible
//  Generator
NEMA MG1, IEEE and ANSI standards compliance for temperature rise
and motor starting
Sustained short circuit current of up to 300% of the rated current for up
to 10 seconds
Self-Ventilated and Drip-Proof
Superior Voltage Waveform
Digital, Solid State, Volts-per-Hertz Regulator
No Load to Full Load Regulation
Brushless Alternator with Brushless Pilot Exciter
4 Pole, Rotating Field
130°C Standby Temperature Rise
1 Bearing, Sealed
Flexible Coupling
Full Amortisseur Windings
125% Rotor Balancing
3-Phase Voltage Sensing
±1% Voltage Regulation
100% of Rated Load - One Step
3% Maximum Harmonic Content
www.DataSheet4U.com



No Preview Available !

3 / //  / 40-GC6NLT1
Application data
//  Engine
Manufacturer
Model
Type
Arrangement
Displacement: Cu In (lit)
Bore: in (cm)
Stroke: in (cm)
Compression Ratio
Rated RPM
Engine Governor
Max Power: Standby: bhp (kWm)
Speed Regulation
Frequency
Air Cleaner
//  Liquid Capacity (Lubrication)
Total Oil System: gal (lit)
Engine Jacket Water Capacity: gal (lit)
System Coolant Capacity: gal (lit)
//  Electrical
Electric Volts DC
Cold Cranking Amps Under 0°F (-17.8°C)
//  Fuel Inlet
Fuel Supply Connection Size
Fuel Supply Pressure: in. H20 (mm H20)
GM
4.3L
4-Cycle
6-V
262 (4.3)
4 (10.2)
3.5 (8.8)
9.4:1
1,800
Bosch
71.4 (53.3)
±1%
60 Hz
Dry
1.1 (4.2)
1.9 (7.2)
5.7 (21.6)
12
600
3/4” NPT
7–11 (178–279)
//  Fuel Consumption (NG-1000 BTU/ft3 / LP-2500 BTU/ft3)
At 100% of Power Rating: ft3/hr (m3/hr)
At 75% of Power Rating: ft3/hr (m3/hr)
At 50% of Power Rating: ft3/hr (m3/hr)
NG
489 (13.9)
368 (10.4)
256 (7.3)
LPG
216 (6.1)
163 (4.6)
113 (3.2)
//  Cooling - Radiator System
Ambient Capacity of Radiator: °F (°C)
122 (50)
Max. Restriction of Cooling Air, Intake,
and Discharge Side of Rad.: in. H20 (kPa)
Water Pump Capacity: gpm (lit/min)
0.5 (0.12)
31 (117.3)
Heat Rejection to Coolant: BTUM (kW)
2,220 (39)
Heat Radiated to Ambient: BTUM (kW)
938 (16.5)
//  Air Requirements
Aspirating: *SCFM (m3/min)
136.5 (3.9)
Air Flow Required for Rad.
Cooled Unit: *SCFM (m3/min)
7,464 (211.4)
Air Flow Required for Heat
Exchanger/Remote Rad. based
on 25°F Rise: *SCFM (m3/min)
2,114 (59.9)
* Air density = 0.0739 lbm/ft3 (1.184 kg/m3)
//  Exhaust System
Gas Temp. (Stack): °F (°C)
1,300 (704.4)
Gas Volume at Stack
Temp: CFM (m3/min)
440.8 (12.5)
Maximum Allowable
Back Pressure: in. H20 (kPa)
40 (10)
www.DataSheet4U.com



No Preview Available !

Weights and dimensions
4 / //  / 40-GC6NLT1
Drawing above for illustration purposes only, based on standard open power 480 volt generator. Lengths may vary with other voltages. Do not use for installation design.
System Dimensions (L x W x H)
OPU
78 x 34 x 48.38 in (1,981 x 864 x 1,229 mm)
Weight (dry)
1,260 lb (572 kg)
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific generator set.
Sound data
Unit Type
OPU (dBA)
WPE - No Sound Attenuation (dBA)
CQE (dBA)
Measurements for sound data are taken at 23 ft (7m).
Standby Full Load
C/F
C/F
C/F
Standby No Load Prime Full Load Prime No Load
C/F
C/F
C/F
Emissions data
Fuel Type THC + NOx
Natural Gas
9.42
Liquid Propane 10.95
CO
29.43
42.91
All units are in g/hp-hr.
Engine meets 40 CFR Part 60/90 specifications.
Rating Definitions and conditions
//  Ambient capability factor at 984 ft (300 m). Consult your
local MTU Onsite Energy Power Generation Distributor for
other altitudes.
//  Standby ratings apply to installations served by a reliable
utility source. The standby rating is applicable to varying
loads for the duration of a power outage. No overload capa-
bility for this rating. Ratings are in accordance with
ISO-3046/1, BS 5514, AS 2789, and DIN 6271.
//  Deration Factor:
Altitude: 3% per 1,000 ft (305 m) above 328 ft (100 m).
Temperature: 1% per 10°F (5.5°C) above 77°F (25°C).
www.DataSheet4U.com
Materials and specifications subject to change without notice.
// Tognum Group Companies: Europe / Middle East / Africa / Latin America / MTU Onsite Energy / 88040 Friedrichshafen / Germany / Phone + 49 7541 90 7060 /
Fax +49 7541 90 7084 / powergenregion1@mtu-online.com // Asia / Australia / Pacific / MTU Onsite Energy / 1, Benoi Place / Singapore 629923 / Republic of Singapore /
Phone + 65 6861 5922 / Fax + 65 6861 3615 / powergenregion2@mtu-online.com // USA / Canada / Mexico / MTU Onsite Energy / 100 Power Drive / Mankato, Minnesota
56001 / USA / Phone + 1 507 625 7973 / Fax + 1 507 625 2968 / powergenregion3@mtu-online.com // Worldwide for HotModule / MTU Onsite Energy / 81663 Munich /
Germany / Phone + 49 89 203042 800 / Fax +49 89 203042 900 / info@cfc-solutions.com //www.mtu-online.com



40-GC6NLT1 datasheet pdf
Download PDF
40-GC6NLT1 pdf
View PDF for Mobile


Related : Start with 40-GC6NLT Part Numbers by
40-GC6NLT1 GAS ENGINE-GENERATOR SET 40-GC6NLT1
MTU Onsite Energy
40-GC6NLT1 pdf

Index :   0   1   2   3   4   5   6   7   8   9   A   B   C   D   E   F   G   H   I   J   K   L   M   N   O   P   Q   R   S   T   U   V   W   X   Y   Z   

This is a individually operated, non profit site. If this site is good enough to show, please introduce this site to others.
Since 2010   ::   HOME   ::   Contact